兩臺或多臺發(fā)電機組并聯(lián)運行操作
眾所周知,主要是為了滿(mǎn)足大負荷或不間斷供電要求、保證瓦斯發(fā)電機組供電的可靠性、提高供電質(zhì)量、增加運行的靈活性,做到經(jīng)濟運行,那么在此類(lèi)情況下往往需要啟動(dòng)兩臺或多臺機組同時(shí)對負載進(jìn)行供電。那么兩臺或多臺發(fā)電機組并聯(lián)運行操作是怎么回事呢?
As we all know, it is mainly to meet the requirements of large load or uninterrupted power supply, ensure the reliability of power supply of gas generating units, improve the quality of power supply, increase the flexibility of operation, and achieve economic operation. In such cases, it is often necessary to start two or more units to supply power to the load at the same time. So what about the parallel operation of two or more generator sets?
瓦斯發(fā)電機組并聯(lián)運行原理
Parallel operation principle of gas generator set
通俗、廣義的理解即就是兩臺或兩臺以上的發(fā)電機組在相位、電壓、頻率一致的情況下,通過(guò)自動(dòng)同步系統(多為同步表)來(lái)實(shí)現的并聯(lián)合閘的動(dòng)作,通過(guò)功率分配器來(lái)分配機組間的負荷承擔,通過(guò)末端負載需求量來(lái)確定投入需并聯(lián)開(kāi)機臺數,直至完成發(fā)電任務(wù)解列空載運行,通過(guò)上述一系列動(dòng)作繼而實(shí)現并聯(lián)運行的全過(guò)程。
In a popular and broad sense, it means that two or more generator units realize the action of combined switch through automatic synchronization system (mostly synchronization meter) under the condition of consistent phase, voltage and frequency, distribute the load between units through power distributor, and determine the number of parallel start-up units required for input through terminal load demand until the power generation task is completed and the no-load operation is disconnected, Through the above series of actions, the whole process of parallel operation is realized.
瓦斯發(fā)電機組并聯(lián)運行條件
Parallel operation conditions of gas generator set
1、應確保待并機組的機況要求非常良好,好是全新設備在出廠(chǎng)前由具有生產(chǎn)、調試并聯(lián)系統資質(zhì)或的廠(chǎng)家定制好,這種如果屬于運行已久或者臨時(shí)購買(mǎi)的機組尤其需要注意:
1. It shall be ensured that the conditions of the units to be combined are very good. The good thing is that the brand-new equipment is customized by the manufacturer with the qualification or patent for production and commissioning of parallel system before leaving the factory. In particular, if the unit has been in operation for a long time or is temporarily purchased, attention shall be paid to:
單臺機組運行時(shí)能確保電壓、頻率、等重要指標在空載運行或負荷下運行均正常。
During the operation of a single unit, it can ensure that the voltage, frequency and other important indicators operate normally under no-load operation or load.
好是同種品牌、同種功率、同種調速方式、調壓方式為自動(dòng)調壓式;特別需要強調的是盡可能的將功率要同等或成比例累加。
The good thing is that the same brand, the same power, the same speed regulation mode and voltage regulation mode are automatic voltage regulation; It should be emphasized that the power should be accumulated equally or proportionally as far as possible.
2、在并聯(lián)運行時(shí)必須避免產(chǎn)生巨大的沖擊電流,以防止同步發(fā)電機組受到損壞、電網(wǎng)遭受干擾。
2. During parallel operation, huge impulse current must be avoided to prevent the synchronous generator unit from being damaged and the power grid from being disturbed.
3、在上述要求均滿(mǎn)足的情況下在電氣上還要滿(mǎn)足以下4個(gè)基本條件:
3. Under the condition that the above requirements are met, the following four basic conditions shall be met electrically:
相序待并發(fā)電機組輸出電壓的相序必須和已運行發(fā)電機組的相序一致;
Phase sequence the phase sequence of the output voltage of the generator set to be paralleled must be consistent with the phase sequence of the operating generator set;
頻率待并發(fā)電機組輸出電壓的頻率和已運行發(fā)電機組的頻率相等;
Frequency the frequency of output voltage of the generator set to be paralleled is equal to the frequency of the generator set already in operation;
電壓待并發(fā)電機組的電壓和已運行發(fā)電機組的電壓相等;
Voltage the voltage of the generator set to be paralleled is equal to that of the generator set already in operation;
相位待并發(fā)電機組輸出電壓的相位和已運行發(fā)電機組電壓的相位相同。
The phase of the output voltage of the generator set to be paralleled is the same as that of the generator set that has been operated.
上述條件不滿(mǎn)足任何一條,都會(huì )因瞬時(shí)值不等而出現環(huán)流。環(huán)流通俗的理解就是機組的空載并聯(lián)的情況下某臺或數臺機組出現視在可見(jiàn)負荷,如果環(huán)流過(guò)大會(huì )導致機組功率虛高而出現過(guò)流保護提前工作的弊病。
If none of the above conditions is satisfied, circulation will occur due to different instantaneous values. The common understanding of circulating current is that under the condition of no-load parallel connection of units, one or several units have apparent load. If the circulating current is too large, the unit power will be falsely high and the overcurrent protection will work in advance.
然而發(fā)電機組并聯(lián)運行也不是一件簡(jiǎn)單的事,以上我們就進(jìn)行了基礎的講解,您可以參考使用,當然要根據實(shí)際情況來(lái)做調整,更多內容的了解就來(lái)我們網(wǎng)站www.elmasticar.com關(guān)注看看看吧!
However, the parallel operation of generator sets is not a simple thing. We have explained the basics above. You can use them for reference. Of course, it should be adjusted according to the actual situation. For more information, please visit our website at www.elmasticar.com Pay attention to it. Www. 68mn!